EOXY Fault

From OPS enCYClopedia
Revision as of 08:57, 2 November 2017 by Kevinmcl (talk | contribs)

Jump to: navigation, search

Procedure
Scope: Site Wide
Type: Controlled
Last Reviewed: Needs Review
References: Gas Monitor Warning Response (Section 7.3.3, page 27)

Description

Manage an EOXY oxygen monitor fault.

Procedure

  • If OM 4, 5, 7, or 8 fail, bypass EOXY:SV01 and EOXY:SV02 and open the valves.
  • If OM 2, 3, or 6 fail, check the status of ELNS:SV01 and contact the E-LINAC cryogenics expert or alternate immediately.
  • Post signs that direct personnel to carry a PODM when entering the area.
  • Submit a Fault Report to the ODH – O2 Depletion group and summarize the events in the 520 MeV Cyclotron Operations E-Log.

Related Information

Oxygen Monitoring System

Personal Oxygen Monitors